Temperature Range: -148 to
1999°F (-100 to 1200°C). Input: Type K thermocouple. Output: Dual alarm rated 1A @ 250VAC, 4-20 mA with 8V max compliance or
0-10 VDC 1k Ω min. Power Requirements: 115/230
VAC, ±10%, 50/60 Hz. Power Consumption: 7W. Accuracy: ±2% at 23°C ambient. Display: 4-digit, red, 1/2" digits. Resolution: 1°F/°C. Operating Temperature: 32 to
122°F (0 to 50°C). Ambient Temperature Effect: +0.01% of rdg., -0.05° per degree. Temperature Coefficient: ±100 Set Point Adjustment: 0 to 2000 counts, adj. within 5 counts or better.
ppm/°C. Read Rate: 2.5 readings/sec. Weight: 1 lb (500 g). Front Panel Rating: 1/8 DIN,
NEMA 12.