Calibration-Free, 2-Wire Design, Duct or Wall Mount
Relative Humidity Range: 10 to 90% RH. Temperature Range: Duct mount: -40 to 140°F (-40 to 60°C),
wall mount: 23 to 131°F (-5 to 55°C). Accuracy: ±3% RH @ 25°C, ±0.3°C @ 25°C. Temperature Limits: Duct mount: 14 to 140°F (-10 to 60°C),
wall mount: 23 to 131°F (-5 to 55°C). Storage Temperature: -40 to 140°F (-40 to 60°C). Operating Humidity Range: Duct mount: 0 to 100% RH, wall mount:
0 to 90% RH. Power Requirements: 10 to 28 VDC. Output Signal: 4 to 20 mA. Response Time: 15 seconds. Current Consumption: 4 mA minimum. Conduit Connection: 1/2" NPT. Mounting Connection: 3/4" NPT. Drift: ±2% RH over 2 years. Temperature Sensor: Pt 1000Ω RTD. RH Temperature Dependence: <±1.5% RH from 14 to 140°F
(-10 to 60°C). Temperature Dependence: 0.01°C/°C. Housing Material: ABS plastic. Enclosure Rating: Duct mount only IP65. Weight: 0.6 lb (0.3 kg). Agency Approvals: CE.