Two Form C (SPDT) Switches, Small Size, Mounts Easily on 35 mm DIN Rail
Power Supply: (SC units) 85 to 265 VDC/VAC 50 to 400 Hz (12-24
VDC, VAC 50-400 Hz for Low Voltage Option, SCL units). Isolation: 1500 V rms between outputs, input, and power. Set Points: Adjustable 0 to 100% of span. Deadband: Adjustable 0.25 to 100% of span. Drift: ±0.02%/°C typical ±0.05%/°C maximum. Ambient Temperature Range: (Operating) 32 to 131°F
(0 to 55°C). (Storage) -40 to 176°F (-40 to
80°C). Excitation Current: (SC1490) Cu10Ω = 5 mA; Plt 100Ω, Ni
100Ω,Ni 120Ω = 500µA; Plt 500Ω, NiFe 1000Ω =
100 µA; Plt 1000Ω = 50 µA. Lead Compensation Error: (SC1490) = 0.02%/Ω. Open Lead Protection: (SC 1490) Upscale only. Input Impedance: (1290) 3 megohms. Sensor Burnout Protection: Selectable, upscale or downscale on 1290. Relay Output: Form C, SPDT, one per set point, 5A @ 250 VAC, resistive. Latch Circuit Reset: Automatic at power up. Manual with reset switch
on front of module. Indicators: One dual color LED per set point. Red = relay on, green
= relay off. Wiring Terminals: Screw driven compression type. Dimensions: 2.95" H x 0.89" W x 3.89" D (75 x 22.5 x 98.5 mm).