Series MTL5041/5045 Galvanic Barrier

Intrinsically Safe Isolators for Hazardous Locations

No longer available, see MTL5541.

Specifications

Hazardous Area Input:
Signal Range: 0 to 24 mA (including over-range); Transmitter Voltage: 16.5 V @ 20 mA.
Safe Area Output:
Signal Range: 4 to 20 mA; Safe-Area Load Resistance: 0 to 1kΩ Safe-Area Output Resistance: >2MΩ.
Power Requirement:
20 to 35 VDC.
Response Time:
Settles to within 10% of final value within 250 µs.
Current Consumption (20 mA signal):
70 mA @ 24 VDC; 85 mA @ 20 VDC; 55 mA @ 35 VDC.
Maximum Power Dissipation (20 mA signal):
1.2 W @ 24 VDC.
Isolation:
250 V rms between input, output and power supply terminals.
Transfer Accuracy at 68°F (20°C):
Better than 20 µA (typically 5 µA).
LED Indicator:
Green: Power Indication.
Temperature Limits:
Operating: -4 to 140°F (-20 to 60°C); Storage: -40 to 176°F (-40 to 80°C).
Temperature Drift:
<1 µA/°C.
Humidity:
5 to 95% RH.
Mounting:
1.4" (35 mm) top hat rail to: EN 50022-35 x 7.5, BS 5584, 35 x 27 x 7.3 DIN 46277.
Terminals:
Accommodate up to 2.5 mm² stranded or single-core.
Safety Description:
28 V, 300Ω, 93 mA; Um=250 rms or dc.
Weight:
3.9 oz (110 g).
Agency Approvals:
See table on Catalog page.

Product Literature

Manuals

Catalog Pages