_PIC.jpg) |
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: Polypropylene/PPS or Polyvinylidene
Fluoride.
Temperature Limits: -40 to 158°F (-40 to 70°C).
Pressure Limits: 150 psi (10 bar) @ 77°F (25°C), derated
1.67 psi (.113 bar) per °C above 25°C.
Relay Output: 1 SPDT Form C, isolated and sealed.
Relay Load: 250 VAC, 10 A resistive, 1/2 hp.
Switching Mode: Selectable NO or NC.
Supply Voltage: 120/240 VAC, 50/60 Hz, selectable.
Current Consumption: .25 amps maximum.
Sensor Voltage Supply: 13 VDC, 1 Watt max., nominal.
Sensor Trigger Point: Dry <10 mA, wet >10 mA.
Time Delay: Adjustable, 0.15 to 60 seconds.
Flash Type: *Xenon tube.
Flash Frequency: *1 per second.
Brightness: *>50,000 CP.
Strobe Life: *10 M cycles.
Conduit Connection: 1/2" NPT.
Mounting Connection: 3/4" NPT.
Enclosure: Polypropylene, flame retardant, probe NEMA 4X/IP65.
Agency Approvals: CSA, CE.
*Applies to models with flash alarm only. |