Home Product Information Free Literature International Distribution What's New About Us Careers Contact Us
Go to the Home page Click to Order New Quick Search
Online Account Access!
E-mail Address:
Password:
Forgot Your Password?

Register Your Account
Search by Series/Model

Series
SC4380
Iso Verter® II Signal Conditioning Module
Accepts Virtually all Standard Process Signals, Easy-to-Wire Surface Mount/DIN Rail Mount, Completely Isolated Input and Output Signals

SPECIFICATIONS
Isolation: 1500 VAC RMS.
Linearity: 0.1% of full scale.
Drift: ±0.02%/°C typical, ±0.05%/°C maximum.
Power Supply: 85 to 265 VDC/VAC 50 to 400 Hz.
Output Loads: Current: 600 ohms maximum; Voltage: 500 ohms minimum (20 mA maximum).
Input Characteristics: Voltage: 1 megohms impedance; Current: 10 ohms.
Case Size: 0.866" W x 2.950" H x 3.880" D (25.0 x 75.0 x 98.5 mm).
Mounting: Mounts on industry standard 35 mm DIN Rail (DIN EN50022-35).

RANGES OF POPULAR MODEL SC4380
Inputs Outputs
Currents Voltage Current Voltage
0 to 5 mA 0 to 100 mV 0 to 1 mA 0 to 1 V
0 to 10 mA 0 to 200 mV 0 to 5 mA 0 to 5 V
0 to 10 mA 0 to 500 mV 0 to 20 mA 0 to 10 V
0 to 20 mA 0 to 1 V 1 to 5 mA 1 to 5 V
0 to 50 mA 0 to 5 V 4 to 20 mA 2 to 10 V
0 to 100 mA 0 to 10 V    
1 to 5 mA 1 to 5 V    
4 to 20 mA 2 to 10 V    
10 to 50 mA      