Power Supply: SC468: 85 to 265 VDC/VAC 50 to 400 Hz; SCL468: 9.6 to 28 VDC/VAC 50 to 400 Hz. Power Consumption: 2VA. Isolation: 1800 VAC. Ambient Temperature Range Operating: 32 to 131°F (0 to 55°C); Storage: -40 to 176°F (-40 to 80°F). Humidity Conditions (non-condensing): 0 to 90% up to 40°C
, 10 to 50% at 55°C. Linearity: 0.1% of span. Drift: ±0.02% per °C typical, ±0.05% maximum. Response Time: 2mS, 90% step change. Input: AC sine wave. Voltage Input: Range: 100 mV to 200 VAC; Input impedance:
100 Kilohm; Overvoltage: 300 VAC. Current Input: Range: 10 mA to 100 mA AC; Input impedance: 10 ohms;
Overcurrent: 120 mA AC. Frequency Range: 40 to 400 Hz. Zero Adjustment: -10% to +50% of scale. Span Adjustment: -50% to +10% of scale. Output Ranges: 0 to 1 V, 0.2 to 1 V, 0 to 5 V, 1 to 5 V, 0 to 10 V,
2 to 10 V, 0 to 1 mA, 0.2 to 1 mA, 0 to 5 mA, 1 to 5 mA, 0 to 10 mA, 2 to
10 mA, 0 to 20 mA, 4 to 20 mA. Current Output Compliance: 12 V. Maximum current Output Load: 600 ohms. Maximum Voltage Output Current (Minimum Voltage Output Load): 20
mA (500 ohms). Weight: 4.5 oz (128 g).