Explosion-proof, Weatherproof, Compatible with Natural Gases
Service: Air and compatible combustible gases. Wetted Materials: Consult factory. Temperature Limits: 0 to 140°F (-17 to 60°C). Note:
Set point drift may occur with ambient temperature changes. Pressure Limits: 45" w.c. (11.2 kPa) continuous; 10 psig (68.95
kPa) surge. Enclosure Rating: NEMA 3 (IP54), NEMA 7 and 9. Switch Type: 1 Form C relay (SPDT). Electrical Rating: 10A, 120/240 VAC, 28 VDC. Resistive 50mA,
125 VDC. Power Requirements: 24 VDC ±10%. 120 or 240 VAC ±10%
optional. Electrical Connections: Internal terminal block. Process Connections: 1/8" female NPT. Mounting Orientation: Diaphragm in vertical position. Consult
factory for other position orientations. Set Point Adjustment: Screw type on top of housing. Weight: 2 lbs. 15.7 oz. (1.35 kg). Agency Approvals: CE, UL, CSA, FM, ATEX.