Duct Pressure Transmitters
±1% FS Accuracy, NEMA 4 (IP56) Enclosure, Three Field Selectable Ranges
Service:
Clean dry air or any inert gas.
Wetted Materials:
Aluminum alloy and nylon.
Accuracy:
±1% FS (includes non-linearity, hysteresis, and non-repeatability).
Temperature Limits:
0 to 175°F (-18 to 80°C).
Pressure Limits:
10 psid (0.7 kg/cm²).
Compensated Temperature Range:
25 to 150°F (-4 to 65°C).
Thermal Errors:
±0.0125%/°F (0.02%/°C).
Power Requirements:
12-40 VDC.
Output:
4-20 mA, 2-wire.
Zero and Span Adjustment:
±15%, non-interactive.
Response Time:
60 msec.
Loop Resistance:
3000 ohms max. @ 40 VDC.
Stability:
< 1% FS/year.
Electrical Connections:
Unpluggable screw terminal block.
Conduit Connection:
1/2" (22.3 mm) knockout.
Enclosure:
Cold-Rolled Steel, NEMA 4 (IP56).
Weight:
1.0 lb (.45 kg).
Agency Approvals:
CE.