Selectable Inputs: Thermocouple (J type stocked), field selectable
K, T,
R, S, E, F, N, or B type; RTD (100 Ω DIN); Current or Voltage. Input Impedance: Thermocouple (1 MΩ min.); RTD Current (1 mA max.);
Current (51 Ω) and Voltage (1 MΩ). Dual Relay Output: DPST with shared common. Fully programmable for High,
Low or Deviation Alarm, deadband, time delay, manual or automatic reset, NO or
NC operation (factory wired NC in power-off state). Contacts rated 8A max., 100
mA
min., @ 240 VAC (<100 mA switching current may require removal of factory wired
varistors across relay contacts) and 8A
max. @ 30 VDC. Current Retransmission Output: Spannable 4-20 mA, 0-20 mA or 0- 10 mA;
0 mA
min.22 mA max.; Loop resistance: 0-700 Ω (integral loop
powered), 0-1000 Ω (externally powered 10-30 VDC). Integral Power Supply (for 4-20 mA, 2-wire transmitter input): 20 VDC,
50 Ω input
impedance. Power Requirements: 120 VAC, 50/60 Hz (as stocked); field configurable
240 VAC 50/60 Hz. Accuracy (@ 20°C): Thermocouple input ±1°C Cold Junction
Error ±1°C
(J, K, T type), ±2°C (R, S, E, F, N type) or ±3°C (B type);
RTD input ±0.1%
of reading ±0.1°C; Current input ±0.1% full span; Voltage input ±0.02%
full span (0.1, 1, 10 volts), ±0.04% full span (1-5 volts). Displays: 5-digit, 7 segment 14 mm (0.5") high LED display; Four independent
alarm status LED indicators; 3.3 Hz update rate. Display Resolution: User-adjustable. Memory Backup: Nonvolatile memory. Serial Communications: Optional RS485. Operating Temperature: 10 to 40°C (Linearized and cold junction
compensated). Electrical Connections: Removable terminal blocks for ease of wiring. Isolation: Power Supply to 1.5 kV; Inputs to 500V; Relay Outputs to 500V;
Current Retransmission Output to 500V (typical). Weight: 1 Ib, 14 oz (850 g). Options: 24 VAC 50/60 Hz Supply Voltage; SPDT Relay Output; Programmable
2-20 VDC or Constant 24 VDC Outputs; RS485 Serial
Communications. Agency Approvals: CE.