The Series EPTA is an electric to pneumatic transducer that converts an analog
input signal to a linearly proportionate pneumatic output by modulating its
control valves to regulate branch line pressure to the set point determined by
the input signal. All models incorporate two low voltage valves, an integral inbarb
filter, a 0 to 30 psi analog gauge, an anodized aluminum manifold, and
brass barbed fittings. The EPTA offers adjustable span and offset as well as
manual override. This unit has no air consumption and is immune to mounting
orientation. Output pressure ranges include field selectable 0 to 10, 0 to 15, and
0 to 20 psig. Also included is an analog 0 to 5 VDC feedback signal indicating
the resultant branch line pressure. Universal 24 VAC/24 VDC supply voltage
and field selectable 4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC, or 0 to 15 VDC inputs
ensure single unit compatibility with most systems. The standard models maintain
branch pressure on power loss while the Fail-Safe models will drop the
branch pressure to 0 psi on power loss. Mounting configurations include a metal
bracket mount in the EPTA-B models and a snap-track mount in the EPTA-S
models. The A-400 accessory kit will allow the EPTA-S models to be mounted
on a standard DIN rail.