Service: Clean dry air or any inert gas. Input Signal: DC Current (4-20 mA) or DC Voltage (0-5/0-10/0-15). Input Impedance:
Current: 250 ohms;
Voltage: Infinite. Output Signal: Jumper selectable 0-10 psig (0-69 kPa), 0-15 psig (0-103
kPa), or 0-20 psig (0-138 kPa). Feedback Output: 0 to 5 VDC. Air Supply: 25 psig (172 kPa) maximum. Air Flow: 750 scim. Air Consumption: 0 scim normal operation, Fail-Safe model vents to 0 psi
on power loss. Accuracy:±1.0% full scale @ room temperature; ±2.0% full scale @ 32 to 120°F (0 to 48.8°C). Supply Voltage: 24 VDC (+10%/-5%) or 24 VAC (±10%) 50/60 Hz. Supply Current: 180 mA maximum, 200 mA maximum on Fail-Safe model. Temperature Limits:
Operating: 32 to 120°F (0 to 48.8°C);
Storage: -20 to 150°F (-6.7 to 65.6°C). Operating Humidity Range: 5 to 95%, non-condensing. Pressure Connections: 1/4" O.D. (polyethylene tubing optimum). Electrical Connections: Plug-in block terminal type with 5mm pin spacing. Wire Size: Up to one 14 AWG per terminal. Weight: EPTA-S0: 6.9 oz. (196 g), EPTA-S1: 9.2 oz. (261 g), EPTA-B: 14.5
oz. (411 g).