Service: Compatible liquids or gases. Body: 2-way. Line Size: 1/2" to 4". End Connections: Female NPT or socket (field selectable). Pressure Limit: 1/2" to 2": 232 psi (16.0 bar) @ 73°F
(23°C); 2-1/2" to 4": 150 psi (10.3 bar) @ 73°F
(23°C)
WOG. Vacuum: 29" Hg. Wetted Materials: Body & End Connections: PVC
or CPVC; Ball & Stem: PVC or CPVC; Seat: TFE; Stem Seal: EPDM. Temperature Limit: 32 to 140°F (0 to 60°C). Other Materials: Stem Bearing: Polypropylene (1-1/4"
and up).
ACTUATORS Electric
Power Requirements: 120 VAC, 50/60 Hz, single phase. Optional 220
VAC, 24 VAC, 12 VDC, and 24 VDC. Power Consumption: (Locked Rotor Current): Two Position:
1/2" to 1-1/2": 0.55A; 2" to 4": 0.75A. Modulating:
1/2" to 2": 0.75A; 2-1/2": 1.1A; 3" to 4": 0.75A. Cycle Time (per 90°): Two Position: 1/2" to
1-1/2": 2.5 sec.; 2" to 2-1/2": 5 sec.; 3" to 4": 15 sec.
Modulating: 1/2" to 2-1/2": 5 sec.; 3" to 4": 15 sec. Duty Cycle: Two Position: 1/2" to 1-1/2":
75%; 2" to 4": 25%. Modulating: 75%. Enclosure Rating: NEMA 4. Optional NEMA 7 (Class 1,
Div. II, Groups A, B, C, D). Housing Material: Aluminum with thermal bonding polyester
powder finish. Temperature Limit: 0 to 150°F (-18 to 65°C). Conduit Connection: 1/2" female NPT. Modulating Input: 4 to 20 mA. Standard Features: Manual override and visual position
indicator except modulating units.
Pneumatic "DA" and "SR" Series
Type: DA series is double acting and SR series is spring return (rack
and pinion). Normal Supply Pressure: 80 psi (5.5 bar). Maximum Supply Pressure: 120 psig (8 bar). Air Connections: DA1 to 5 and SR2 to 5: 1/8" femal NPT; all others: 1/4" female NPT. Air Consumption (per stroke): DA1: 2.32 cu. in.;
DA2: 9.34 cu. in.; DA3: 17.21 cu. in.; DA4: 20.5 cu. in.; SR2: 9.34
cu. in.; SR3: 17.21 cu. in.; SR6: 54.34 cu. in.; SR7: 85.43 cu. in. Cycle Time (per 90°): DA1: .03 sec.; DA2: .04
sec.; DA3: .08 sec.; DA4: .12 sec.; SR2: .09 sec.; SR3: .14 sec.;
SR6: .46 sec.; SR7: .83 sec. Housing Material: Anodized aluminum body and epoxy
coated aluminum end caps. Temperature Limit: -4 to 180°F (-20 to 82°C). Accessory Mounting: NAMUR standard. Standard Features: Visual position indicator.