Series MS Magnesense® Differential Pressure Transmitter
Monitors Pressure & Air Velocity
The Series MS Magnesense® Differential Pressure Transmitter is an extremely versatile transmitter for monitoring pressure and air velocity. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output signal (with optional display) and the ability to select a square root output for use with Pitot tubes and other similar flow sensors.
Along with these features, the magnetic sensing technology provides exceptional long term performance and enables the Magnesense® transmitter to be the solution for a myriad of pressure and flow applications.
Please see SERIES AT2MS for ATEX approved.
Product Applications
- Building pressure monitoring
- Duct pressure monitoring
- Fan velocity measurement
- Zone differential pressure monitoring
- Filter condition monitoring
Models & Ordering
Specifications
- Service:
- Air and non-combustible compatible gases.
- Wetted Materials:
- Consult factory.
- Accuracy:
- ±1% for 0.25" (50 Pa), 0.5" (100 Pa), 2" (500 Pa), 5" (1250 Pa), 10" (2 kPa), 15" (3 kPa), 25" (5 kPa) ±2% for 0.1" (25 Pa), 1" (250 Pa) and all bidirectional ranges.
- Stability:
- ±1% FS/year.
- Temperature Limits:
- 0 to 150°F (-18 to 66°C).
- Pressure Limits:
- 1 psi maximum, operation; 10 psi, burst.
- Power Requirements:
- 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
- Output Signals:
- 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire).
- Response Time:
- Field adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
- Zero & Span Adjustments:
- Digital push button.
- Loop Resistance:
- Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 kΩ.
- Current Consumption:
- 40 mA max.
- Display (optional):
- 4 digit LCD.
- Electrical Connections:
- 4-20 mA, 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V, 3-wire: European Style Terminal Block 16 to 22 AWG.
- Electrical Entry:
- 1/2" NPS Thread. Accessory: Cable Gland for 5 to 10 mm diameter cable.
- Process Connection:
- 3/16" (5 mm) ID tubing. Maximum OD 9 mm.
- Enclosure Rating:
- NEMA 4X (IP66).
- Mounting Orientation:
- Diaphragm in vertical position.
- Weight:
- 8.0 oz (230 g).
- Agency Approvals:
- CE.
Features
- Field selectable English or Metric ranges
- Field upgradeable LCD display
- Adjustable damping of output signal (with optional display)
- Ability to select a square root output for use with pitot tubes and other similar flow sensors
Options
- Add -LCD to end of model numbers for units with display
Example: MS-121-LCD - Add -NIST to end of model numbers for NIST Traceable Certificate
Example: MS-021-NIST - Add -FC to end of model numbers for Factory Calibration Certificate
Example: MS-021-FC - Add -DS to end of model number for dessicant cover, (not compatible with LCD option)
Example: MS-021-DS
Accessories
Model Number | Description | Usually Ships* | Price | Order | |
---|---|---|---|---|---|
![]() |
A-435 | Field upgradeable LCD. | Same Day | $50.00 | Order |
![]() |
A-489 | 4" 303 SS straight static pressure tip with flange. | Same Day | $6.90 | Order |
![]() |
SCD-PS | 100 to 240 VAC/VDC to 24 VDC power supply. | Same Day | $31.00 | Order |
![]() |
A-481 | Installer kit, (includes 2 static pressure tips and PVC tubing). | Same Day | $4.40 | Order |
![]() |
A-302F-A | 303 SS Static pressure tip with mounting flange, for 3/16" I.D. rubber or plastic tubing. 4" insertion depth, includes mounting screws | Same Day | $9.50 | Order |
![]() |
A-480 | Plastic static pressure tip. | Same Day | $0.90 | Order |
Videos
Model Chart
EXAMPLE | MS | 0 | 2 | 1 | AT | Series MS-021-AT Magnesense® Differential Pressure Transmitter, bidirectional unit, 4-20 mA output, low range 0.1, 0.25, 0.5" w.c. & 25, 50, 100 Pa, wall mount, with aluminum tag. |
SERIES | MS | Magnesense® Differential Pressure Transmitter | ||||
OUTPUT | 0 1 2 3 6 7 8 9 |
Bidirectional Unit, 4-20 mA Positive Only Unit, 4-20 mA Bidirectional Unit, 0-10 V Positive Only Unit, 0-10 V Bidirectional Unit, 0-5 V Positive Only Unit, 0-5 V Bidirectional Unit, 0-5 V Output 0-12VDC Input Positive Only Unit, 0-5V Output 0-12 VDC Input |
||||
RANGE | 1 2 3 4 5 |
High Range 1, 2, 5" w.c. & 250, 500, 1250 Pa Low Range 0.1, 0.25, 0.5" w.c. & 25, 50, 100 Pa Piezo 10" w.c. & 2 kPa Piezo 15" w.c. & 3 kPa Piezo 25" w.c. & 5 kPa |
||||
MOUNTING | 1 2 3 |
Wall Mount Duct Mount Din Mounting Bracket |
||||
OPTIONS | AT DJE DJM DS GLD LCD NIST ST WO |
Aluminum Tag Velocity Mode Selectable Decimal Place (English Units) Velocity Mode Selectable Decimal Place (Metric Units) Dessicant Cover (not available) Cable Gland Accessories Pack Liquid Crystal Display NIST Calibration Certificate Stainless Steel Tag LCD Cover w/o LCD Display |
Note: Not all model combinations are available.
Product Literature
Manuals
Catalog Pages
Product Data Sheet
Approvals
Drawings
Photo Downloads
You must be logged in to view this content.Click here to login to your account.