Series 16L Limit Control
FM Approved, Large Dual Display, Universal Input
The Series 16L Temperature/Process Control offers FM approved limit control with universal input, single set point or dual set point control.
Product Applications
- Gas fired heater limit control
Models & Ordering
Specifications
- Selectable Input:
- 10 Thermocouple, 4 RTD, DC Voltage, or DC current selectable.
- Display:
- Two 4 digit, 7 segment 0.3" (7.62 mm) high LEDs.
- Accuracy:
- ±0.25% of span, ±1 least significant digit.
- Power Requirements:
- 100 to 240 VAC, nominal, +10 - 15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal, +10 - 20%.
- Power Consumption:
- 5 VA maximum.
- Temperature Limits:
- 14 to 131°F (-10 to 55°C).
- Memory Backup:
- Nonvolatile memory. No batteries required.
- Output:
- Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive.
- Weight:
- 8 oz (227 g).
- Front Panel Rating:
- NEMA 4X (IP66).
- Agency Approvals:
- FM, cULus.
Features
- Remote or integral reset button
- Peak and valley temperature indication
- Open sensor protection
Options
- -934, Process Signal Output, Isolated 0 to 20 mADC.
- -936, Process Signal Output, Isolated 0 to 10 VDC.
- -992, RS-485 Serial Communications
- -993, RS-232 Serial Communications
Accessories
Model Number | Description | Usually Ships* | Price | Order | |
---|---|---|---|---|---|
![]() |
A-600 | R/C snubber (recommended for inductive loads like a solenoid or contactor). | Same Day | $20.00 | Order |
A-TC-K100-FB | K type, 100' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $68.50 | Order | |
A-TC-K100-FEP | K type, 100' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $58.50 | Order | |
A-TC-K25-FB | K type, 25' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $25.25 | Order | |
A-TC-K25-FEP | K type, 25' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $23.25 | Order | |
A-TC-K50-FB | K type, 50' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $40.25 | Order | |
A-TC-K50-FEP | K type, 50' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $34.75 | Order | |
A-TC-J100-FB | J type, 100' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $42.25 | Order | |
A-TC-J100-FEP | J type, 100’ on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $31.75 | Order | |
A-TC-J25-FB | J type, 25' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $19.25 | Order | |
A-TC-J25-FEP | J type, 25' on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $16.00 | Order | |
A-TC-J50-FB | J type, 50' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $26.75 | Order | |
A-TC-J50-FEP | J type, 50’ on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $21.25 | Order |
Model Chart
EXAMPLE | 16L | 201 | 0 | 934 | Series 16L2010-934 Limit Control, SSR output A, with set point/process signal output 0-20 mA. |
SERIES | 16L | Limit Control | |||
OUTPUT A | 201 202 203 204 208 |
SSR 15 VDC N.O. Relay N.C. Relay DC-SSR |
|||
OUTPUT B | 0 1 2 3 4 |
None SSR 15 VDC N.O. Relay N.C. Relay |
|||
OPTIONS | 934 936 948 992 993 |
Set Point/Process Signal Output 0-20 mA Set Point/Process Signal Output 0-10 VDC 4-Stage Set Point RS-485 Computer Compatible Control RS-232 Computer Compatible Control |
Approvals
Software
Drawings
Questions
- Question
- We are trying to program a temperature control and receive the following message - Communication error > address 01: no response from controller at register 795 (031A). What could be causing this error?
- Answer
- The register 795 is a Modbus register. One of the reasons why there is a communication error is the -992 for the RS-485 communication is LOVELINK Protocol, if you are trying to communicate with Modbus® protocol, it will not work. See the LoveLink™III Software.
Photo Downloads
You must be logged in to view this content.Click here to login to your account.
Product Reviews